INSTALLATION INSTRUCTIONS
AND
OWNER'S MANUAL
FAN TYPE
DIRECT VENT
WALL FURNACE
For Installation in
Manufactured (Mobile Home),
Modular or Residential Homes
MODELS
DV-20E-5
Patent # 5.664.555
DV-40E-5
Installer: Leave these instructions with the con-
sumer.
Consumer: Retain these instructions for future
use.
WARNING: If the information in this manual
is not followed exactly, a fire or explosion may
resultcausingpropertydamage, personalinjury
or loss of life.
EFFECTIVE DATE
JUNE 2006
—Donotstoreorusegasolineorotherflammable
vapors and liquids in the vicinity of this or
any other appliance.
This appliance may be installed as an OEM
installationinamanufacturedhome(USAonly)
or mobile home and must be installed in ac-
cordancewiththemanufacturer'sinstructions
andtheManufacturedHomeConstructionand
SafetyStandard,Title24CFR,Part3280,inthe
United States, or the Mobile Home Standard,
CAN/CSA Z240 MH Series, in Canada.
— WHAT TO DO IF YOU SMELL GAS
•
•
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier
from a neighbor's phone. Follow the
gas supplier's instructions.
•
•
This appliance is only for use with the type(s)
of gas indicated on the rating plate. A conver-
sion kit is supplied with the appliance.
If you cannot reach your gas supplier,
call the fire department.
WARNING: If not installed, operated and main-
tained in accordance with the manufacturer's
instructions, this product could expose you to
substances in fuel or from fuel combustion which
can cause death or serious illness.
— Installation and service must be performed
byaqualifiedinstaller,serviceagencyorthe
gas supplier.
19562-1-0606
Page 1
IMPORTANT SAFETY INFORMATION
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANEL INSTALLED.
•
•
Due to high temperatures the appliance should be located
out of traffic and away from furniture and draperies.
SERVICE PERSON. The appliance should be inspected
before use and at least annually by a qualified service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding materials, etc. It
is imperative that control compartments, burners and
circulating air passageways of the appliance be kept
clean.
Children and adults should be alerted to the hazards of
high surface temperatures and should stay away to avoid
burns or clothing ignition.
•
•
•
Young children should be carefully supervised when they
are in the same room as the appliance.
•
•
DO NOT put anything around the furnace that will
obstruct the flow of combustion and ventilation air.
Clothingorotherflammablematerialshouldnotbeplaced
on or near the appliance.
DO keep the appliance area clear and free from
combustible material, gasoline and other flammable
vapors and liquids.
Any safety screen or guard removed for servicing an
appliance must be replaced prior to operating the
appliance.
•
•
•
DO examine venting system periodically and replace
damaged parts.
•
•
•
Keep burner and control compartment clean.
Vent cap hot while furnace is in operation.
DO make a periodic visual check of burner. Clean and
replace damaged parts.
For manufactured home (USA only) or mobile home or
residential installation convertible for use with natural
gasandliquefiedpetroleumgaseswhenprovisionismade
for the simple conversion from one gas to the other.
DO NOTuse this heaterif any part has been underwater.
Immediately call a qualified service technician to inspect
the heater and to replace any part of the control system
and any gas control which has been under water.
•
Installation and repair should be done by a QUALIFIED
19562-1-0606
Page 3
SAFETY INFORMTION FOR USERS OF LP-GAS
Propane (LP-Gas) is a flammable gas which can cause fires and
of your household. Someday when there may not be a minute to
lose, everyone's safety will depend on knowing exactly what to
do. If, after reading the following information, you feel you still
need more information, please contact your gas supplier.
explosions. In its natural state, propane is odorless and colorless.
You may not know all the following safety precautions which can
protect both you and your family from an accident. Read them
carefully now, then review them point by point with the members
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
•
•
Donotoperateelectricswitches,lightmatches,useyourphone.
Do not do anything that could ignite the gas.
Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
•
Use your neighbor's phone and call a trained LP-Gas service
person and the fire department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
•
•
Close all gas tank or cylinder supply valves.
•
Finally, let the service man and firefighters check for escaped
gas. Have them air out the area before you return. Properly
trained LP-Gas service people should repair the leak, then
check and relight the gas appliance for you.
LP-Gas is heavier than air and may settle in low areas such as
basements. When you have reason to suspect a gas leak, keep
out of basementsand other low areas. Stay out untilfirefighters
declare them to be safe.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must find out if you
can smell the odorant in propane. Smoking can decrease your
ability to smell. Being around an odor for a time can affect your
sensitivity or ability to detect that odor. Sometimes other odors
in the area mask the gas odor. People may not smell the gas odor
or their minds are on something else. Thinking about smelling a
gas odor can make it easier to smell.
in LP-Gas also are subject to oxidation. This fading can occur if
there is rust inside the storage tank or in iron gas pipes.
Theodorantinescapedgascanadsorborabsorbontoorintowalls,
masonry and other materials and fabrics in a room. That will take
some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could
vary at different levels. Since it is heavier than air, there may be
more odor at lower levels.Always be sensitive to the slightest gas
odor. If you detect any odor, treat it as a serious leak. Immediately
go into action as instructed earlier.
The odorant in LP-gas is colorless, and it can fade under some
circumstances. For example, if there is an underground leak, the
movement of the gas through soil can filter the odorant. Odorants
SOME POINTS TO REMEMBER
•
•
•
•
Learn to recognize the odor of LP-gas. Your local LP-Gas
Dealer can give you a "Scratch and Sniff" pamphlet. Use it to
find out what the propane odor smells like. If you suspect that
your LP-Gas has a weak or abnormal odor, call your LP-Gas
Dealer.
reinstalled old tanks, if they are filled and allowed to set too
long before refilling. Cylinders and tanks which have been out
ofserviceforatimemaydevelopinternalrustwhichwillcause
odor fade. If such conditions are suspected to exist, a periodic
sniff test of the gas is advisable. If you have any question about
the gas odor, call your LP-gas dealer. A periodic sniff test of
the LP-gas is a good safety measure under any condition.
Ifyouarenotqualified,donotlightpilotlights,performservice,
or make adjustments to appliances on the LP-Gas system. If
you are qualified, consciously think about the odor of LP-Gas
prior to and while lighting pilot lights or performing service
or making adjustments.
•
•
If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the same
immediate action recommended above for the occasion when
you do detect the odorized LP-Gas.
Sometimes a basement or a closed-up house has a musty smell
that can cover up the LP-Gas odor. Do not try to light pilot
lights, perform service, or make adjustments in an area where
the conditions are such that you may not detect the odor if
there has been a leak of LP-Gas.
If you experience a complete "gas out," (the container is under
no vapor pressure), turn the tank valve off immediately. If the
container valve is left on, the container may draw in some air
through openings such as pilot light orifices. If this occurs,
some new internal rusting could occur. If the valve is left
open, then treat the container as a new tank. Always be sure
your container is under vapor pressure by turning it off at the
container before it goes completely empty or having it refilled
before it is completely empty.
Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people should
be particularly alert and careful when new tanks or cylinders
are placed in service. Odor fade can occur in new tanks, or
Page 4
19562-1-0606
REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment
3. SIGNAGE.Ametalorplasticidentificationplateshall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in
line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2)
inchinsize,“GASVENTDIRECTLYBELOW.KEEP
CLEAR OF ALL OBSTRUCTIONS”.
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but
not limited to decks and porches, the following requirements
shall be satisfied:
1. INSTALLATIONOFCARBONMONOXIDEDETEC-
TORS.Atthetimeofinstallationofthesidewallhorizontal
vented gas fueled equipment, the installing plumber or
gasfittershallobservethatahardwiredcarbonmonoxide
detector with an alarm and battery back-up is installed on
the floor level where the gas equipment is to be installed.
Inaddition,theinstallingplumberorgasfittershallobserve
that a battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional
level of the dwelling, building or structure served by
the side wall horizontal vented gas fueled equipment. It
shallbetheresponsibilityofthepropertyownertosecure
the services of qualified licensed professionals for the
installation of hard wired carbon monoxide detectors
4. INSPECTION. The state or local gas inspector of the
side wall horizontally vented gas fueled equipment shall
not approve the installation unless, upon inspection, the
inspectorobservescarbonmonoxidedetectorsandsignage
installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS:Thefollowingequipmentisexempt
from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the
most current edition of NFPA 54 as adopted by
the Board; and
2. ProductApproved side wall horizontally vented
gas fueled equipment installed in a room or
structure separate from the dwelling, building or
structure used in whole or in part for residential
purposes.
a. Inthe event thatthe side wall horizontallyvented gas
fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with
alarm and battery back-up may be installed on the
next adjacent floor level.
(c) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side
wall horizontally vented gas equipment provides a
ventingsystemdesignorventingsystemcomponents
with the equipment, the instructions provided by the
manufacturer for installation of the equipment and
the venting system shall include:
b. In the event that the requirements of this subdivision
can not be met at the time of completion of installa-
tion, the owner shall have a period of thirty (30) days
to comply with the above requirements; provided,
however, that during said thirty (30) day period, a
battery operated carbon monoxide detector with an
alarm shall be installed.
1. Detailed instructions for the installation of the
venting system design or the venting system
components; and
2. APPROVED CARBON MONOXIDE DETECTORS.
Eachcarbonmonoxidedetectorasrequiredinaccordance
with the above provisions shall comply with NFPA 720
and be ANSI/UL 2034 listed and IAS certified.
2. Acompletepartslistfortheventingsystemdesign
or venting system.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for
ventinginstructions,and/orallventingdesigninstruc-
tions shall remain with the appliance or equipment
at the completion of the installation.
19562-1-0606
Page 5
INTRODUCTION
Introduction
to physical damage by a moving vehicle.
Always consult your local Building Department regarding
regulations, codes or ordinances which apply to the installation of
a direct vent wall furnace.
Qualified Installing Agency
Installationandreplacementofgaspiping,gasutilizationequipment
or accessories and repair and servicing of equipment shall be
performed only by a qualified agency. The term "qualified agency"
meansanyindividual, firm, corporationorcompanywhicheitherin
person or through a representative is engaged in and is responsible
for (a) the installation or replacement of gas piping or (b) the
connection, installation, repair or servicing of equipment, who is
experienced in such work, familiar with all precautions required
and has complied with all the requirements of the authority having
jurisdiction.
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installermusthaveownerfilloutandmailwarrantycardsupplied
with furnace.
3. Installer should show owner how to start and operate furnace
and thermostat.
4. Installer must locate unit near a grounded wall receptacle for
115VAC power and must provide gas supply and vent the unit
properly for safe operation.
State of Massachusetts: The installation must be made by
a licensed plumber or gas fitter in the Commonwealth of
Massachusetts.
Warning:
Any change to this furnace or its control can be dangerous.
This is a heating appliance and any panel, door or guard
removed for servicing an appliance must be replaced prior
to operating the appliance.
The installation must conform with local codes, or in the absence
of local codes, the National Fuel Gas Code,ANSI Z223.1/NFPA54
or Natural Gas and Propane Installation Code, CSA B149.1.
*Available from the American National Standards Institute, Inc.,
11 West 42nd St., New York, NY 10036.
General Information
ThisseriesisdesigncertifiedinaccordancewithAmericanNational
Standard/CSA Standard Z21.86 and CSA 2.32 by the Canadian
Standards Association as a Fan Type Direct Vent Wall Furnace to
be installed according to these instructions.
Amanufacturedhome(USAonly)ormobilehomeOEMinstallation
mustconformwiththeManufacturedHomeConstructionandSafety
Standard, Title 24 CFR, Part 3280, or, when such a standard is not
applicable,theStandardforManufacturedHomeInstallations,ANSI
Z225.1, or Standard for Gas Equipped Recreational Vehicles and
Mobile Housing, CSA Z240.4.
Any alteration of the original design, installed other than as
shownintheseinstructionsorusewithatypeofgasnotshownon
the rating plate is the responsibility of the person and company
making the change.
High Altitudes
Foraltitudes/elevationsabove2,000feet(610m),inputratingsshould
be reduced at the rate of 4 percent for each 1,000 feet (305m) above
sealevel, thismaybeaccomplishedbyreducingmanifoldpressure.
ThemaximumallowablereductioninmanifoldpressureforNatural
gas shall be from 3.5" w.c. (.872kPa) to 2.8" w.c. (.697kPa). The
maximum allowable reduction in manifold pressure for Propane
(LP) gas shall be from 10.0" w.c. (2.49kPa) to 8.0" w.c. (1.99kPa).
For Canadian high altitude applications, this appliance is suitable
for installation at elevations between 0 feet (0m) and 4,500 feet
(1,372m) without change.
Important
AllcorrespondenceshouldrefertocompleteModelNumber, Serial
Number and type of gas.
Notice:Duringinitialfiringofthisunit, oilfromtheheatexchanger
maybakeoutandsmokemayoccur.Topreventtriggeringofsmoke
alarms, ventilate the room in which the unit is installed.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed
so that all burners and burner ignition devices are located not less
than 18" (457mm) above the floor.
Such equipment shall be located, or protected, so it is not subject
SPECIFICATIONS
Accessories
Model
DV-20E
DV-40E
Extended Vent Terminal
DVT-2
DVE-1
Input BTU/HR (KW/H) 20,000 (5.9)
40,000 (11.7)
26" (660mm)
37" (940mm)
For walls up to 32" (813mm)
Height
26" (660mm)
37" (940mm)
Intake/Exhaust Extension Kit
Width
54" (1371mm) Vent Kit with 2 Elbows
Depth with Shroud
Gas Inlet (Pipe)
15 3/4" (400mm) 15 3/4" (400mm)
1/2" (13mm) 1/2" (13mm)
54" (1371mm) Vent Kit (straight)
for Extended Vent Runs
DVE-2
(use with DVE-1)
Electrical - Unit as a 5' (1.5m) 3 pronged cordset for connec-
tion to an approved 115 VAC 60HZ maximum
AMPs - 5A wall receptacle.
Floor Pad
DVP-1
Page 6
19562-1-0606
GAS SUPPLY
Amanual main gas cock should be located in the vicinity of the unit.
Wherenoneexists, orwhereitssizeorlocationisnotadequate, con-
tact your local authorized installer for installation or relocation.
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/
CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Pipe Length
Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat.
1/2”
L.P.
Nat.
1/2”
L.P.
0-10 feet
3/8”
3/8”
0-3 meters
12.7mm 9.5mm 12.7mm 9.5mm
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
10-40 feet
1/2” 1/2” 5/8” 1/2”
4-12 meters 12.7mm 12.7mm 15.9mm 12.7mm
40-100 feet 1/2” 1/2” 3/4” 1/2”
13-30 meters 12.7mm 12.7mm 19mm 12.7mm
100-150 feet 3/4” 1/2” 7/8” 3/4”
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required by
the National Fuel Gas Code that a drip line be installed near the gas
inlet. This should consist of a vertical length of pipe tee connected
into the gas line that is capped on the bottom in which condensation
and foreign particles may collect.
31-46 meters 19mm 12.7mm 22.2mm 19mm
Note: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.
Pressure Testing of the Gas Supply System
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
1. To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T.
plugged tapping, accessible for test gauge connection, must be
placed immediately upstream of the gas supply connection to
the appliance.
2. The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/2
psig (3.5 kPa).
3. The appliance must be isolated from the gas supply piping
systembyclosingitsindividualmanualshutoffvalveduringany
pressure testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig (3.5 kPa).
The use of the following gas connectors is recommended:
— ANSZ21.24ApplianceConnectorsofCorrugatedMetalTubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
havingjurisdiction.ThestateofMassachusettsrequiresthataflexible
appliance connector cannot exceed three feet in length.
Attention! If one of the procedures results in pressures in excess
of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will
result in a hazardous condition.
Checking Manifold Pressure
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a manifold
pressure of approximately 3.5" w.c. (.872kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 5.0" w.c.
(1.245kPa) for the purpose of input adjustment to a maximum of
10.5" w.c. (2.614kPa) Propane gas models will have a manifold
pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 11.0" w.c.
(2.739kPa) for the purpose of input adjustment to a maximum of
13.0" w.c. (3.237kPa).
A 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge
connection, is located on the outlet side of the gas control.
Figure 1
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
19562-1-0606
Page 7
GAS CONVERSION INSTRUCTIONS
Warning: Conversion must be done by a qualified service technician. Main burner orifice(s) and new
gas conversion label are provided in conversion kit attached to manifold pipe.
CONVERSION INSTRUCTIONS FROM (LP) PROPANE GAS TO NATURAL GAS
1. Make sure gas supply to furnace is off prior to conversion and disconnect electrical power to unit.
2. Open brass union located between the gas valve and burner box. Re-
VINYL CAP
GAS CONTROL LEVER SHOWN
IN "OFF" POSITION
move the 4 mounting screws securing manifold plate to the burner box.
CONVERTIBLE
REGULATOR
RED LP RING
Remove the top 2 screws holding the burner box top in place and then
remove the 1 screw holding the end of the manifold pipe in place. Grasp
union and remove manifold pipe.
OFF
3. Remove (1) LPgas main burner orifice marked 55 for DV-20E or (2) LP
gas main burner orifices marked 55 for DV-40E located in the manifold
pipe and replace with (1) Natural gas main burner orifice marked 44 for
DV-20E or (2) Natural gas main burner orifices marked 44 for DV-40E
supplied in conversion kit.
TOP VIEW
BACK END VIEW
4. Replace manifold pipe being sure to locate orifice(s) in the end of the burner. Secure the manifold and top burner box cover in
place using the screws earlier removed. Reconnect the brass union.
5. Remove the vinyl cap and unscrew the gas control convertible regulator and reverse to Natural gas side and screw back into place.
The red LP ring will be up just under the vinyl cap. Reattach vinyl cap. Refer to figure illustrating the gas valve.
6. Place LP gas main burner orifice(s) in conversion kit. Attach conversion kit to manifold pipe. Attach new label to unit nameplate
indicating that the unit was converted to Natural gas.
7. Turn on gas supply to furnace and check all gas connections for leaks with soap solution, watching for bubbles on all gas connec-
tions.
8. Turn on electrical power to unit and turn on furnace to verify proper operation. It may take several tries for ignition to completely
purge all the air from the gas line.
Warning: Conversion must be done by a qualified service technician. Main burner orifice(s) and new
gas conversion label are provided in conversion kit attached to manifold pipe.
CONVERSION INSTRUCTIONS FROM NATURAL GAS TO (LP) PROPANE GAS
1. Make sure gas supply to furnace is off prior to conversion and disconnect electrical power to unit.
VINYL CAP
GAS CONTROL LEVER SHOWN
IN "OFF" POSITION
2. Open brass union located between the gas valve and burner box. Remove
the4mountingscrewssecuringmanifoldplatetotheburnerbox. Remove
CONVERTIBLE
REGULATOR
RED LP RING
the top 2 screws holding the burner box top in place and then remove the
1 screw holding the end of the manifold pipe in place. Grasp union and
remove manifold pipe.
OFF
3. Remove (1) Natural gas main burner orifice marked 44 for DV-20E or
(2) Natural gas main burner orifices marked 44 for DV-40E located in
the manifold pipe and replace with (1) LPgas main burner orifice marked
55 for DV-20E or (2) LP gas main burner orifices marked 55 for DV-40E
supplied in conversion kit.
TOP VIEW
BACK END VIEW
4. Replace manifold pipe being sure to locate orifice(s) in the end of the burner. Secure the manifold and top burner box cover in
place using the screws earlier removed. Reconnect the brass union.
5. Remove the vinyl cap and unscrew the gas control convertible regulator and reverse to LP gas side (red ring on regulator) and screw
back into place. Reattach vinyl cap. Refer to figure illustrating the gas valve.
6. Place Natural gas main burner orifice(s) in conversion kit. Attach conversion kit to manifold pipe. Attach new label to unit name-
plate indicating that the unit was converted to LP gas.
7. Turn on gas supply to furnace and check all gas connections for leaks with soap solution, watching for bubbles on all gas connec-
tions.
8. Turn on electrical power to unit and turn on furnace to verify proper operation. It may take several tries for ignition to completely
purge all the air from the gas line.
Page 8
19562-1-0606
CLEARANCES
1. Pick a location on a wall with a clear space of 36" (91.4cm)
The vent terminal of a direct vent appliance, with an input of
50,000 BTU (14.6KW) per hour or less shall be located at least 9"
(229mm) from any opening through which flue gases could enter
a building.
high by 43" (109cm) wide in the room. In selecting a location
for installation, it is necessary to provide adequate accessibility
clearancesforservicingandproperinstallation. Besuretolocate
the unit close enough to a 115 VAC wall receptacle to properly
power appliance.
The bottom of the exhaust vent terminal and the air intake shall
be located at least 12" (305mm) above grade and must be vented
outside.
2. Unit is supported by a wall bracket secured to the wall.
3. When facing the front of the furnace the minimum clearances
from casing to combustible construction are 10" (254mm) on
top, 3" (76mm) on each side, recommend 18" (457mm) on right
side for servicing and 0" (0mm) from the floor and 0" (0mm)
to rear wall.
4. Theblackflockedexhaustpipe,containedinDVE-1KitorDVE-
2 Kit, has zero (0") inches (0mm) clearance to combustibles.
5. The minimum distance from the center of the vent cap to the
nearest outside corner or obstruction is 12" (305mm).
6. The minimum wall depth is 2" (51mm) and the maximum is
10" (254mm) [or 32"(813mm) using the extended vent terminal
kit accessory]. The use of vent tubes not supplied by the
manufacturer may result in unsatisfactory performance.
WARNING: The nearest point of the vent cap should be
a minimum horizontal distant of six (6) feet (1.83m) from
any pressure regulator. In case of regulator malfunction,
the six (6) feet (1.83m) distance will reduce the chance of
gas entering the vent cap.
Installation on Rugs and Tile
If this appliance is to be installed directly on carpeting, tile, or other
combustible material, other than wood flooring, the appliance shall
be installed on a metal or wood panel extending the full width and
depth of the appliance.
The base referred to above does not mean the fire-proof base as
used on wood stoves. The protection is primarily for rugs that may
be extremely thick and light-color tile that can discolor.
FURNACE INSTALLATION
Locating Wall Opening (Figures 2, 3 and 4)
The recommended location for this furnace is on an outside wall.
(The unit can be located on an inside wall but must be vented
using the extended vent kit and should not exceed 15' (4.6m) in
exhaust vent length.) Locate wall studs so that wall vent opening
will be located between wall studs. The wall studs can be used for
attachment of wall mounting bracket. The wall opening required
for venting is a 3 1/4" (83mm) minimum diameter opening.
RefertoFigure2forpositioningthefurnaceonwallandforlocating
gas line connection and vent opening. Furnace can sit on the floor
and should be secured to the wall through the wall bracket secured
to the rear top shroud.
MAY BE 20" TO 13"
TO AVOID STUD
20" (508mm)
12 5/16"
(313 mm)
Figure 3
WALL
2" (51mm) TO 13" (330mm)
3 1/4" (83mm) DIA. VENT
HOLE THRU OUTSIDE WALL
2" (51mm) TO 32" (813mm)
1/2" (13mm) DIA.
GAS SUPPLY
FLOOR TO
BOTTOM OF
WALL BRACKET
17 11/16"
(449mm)
10 1/2"
8 3/4"
(222mm)
3"
(76mm)
(267mm)
FRONT OF FURNACE
Figure 2
Figure 4
19562-1-0606
Page 9
Installing Wall Bracket (Figures 5 and 6)
After finding a location for the furnace, gas supply and vent, the
wall bracket must be positioned and installed. The bracket should
be mounted to the wall studs, if possible, or anchored solidly to the
wall. Use the (2) 10 x 1" (25mm) hex-head screws or (2) plastic
anchors provided. Drill (2) 5/16" (8mm) diameter holes in wall if
plastic anchors are used. Attach the two wall mounting brackets
to the casing back by using (4) 10 x 1/2" (13mm) hex-head screws
provided.
EXHAUST AIR
ORANGE SILICONE
ELBOW CONNECTOR
INTAKE AIR
BLACK FLEXIBLE HOSE
Figure 8
SILICONE COUPLING
HOSE CLAMP
VENT TUBING
EDGE
HOSE CLAMP
EXHAUST CONNECTIONS
Figure 5
4" (102mm)
CASING
WALL
INTAKE FLEX HOSE CONNECTION
WITH INTERNAL METAL COUPLING
WALL MOUNTING BRACKET
BACK
#10 X 1"
VENT COUPLING CONNECTIONS
EXTENDED VENT
#10 X 1/2"
Figure 9
WALL
BRACKET
Venting (Figures 7, 8 and 9)
#10 X 1/2"
This unit is vented directly out the back using the concentric vent
tube assembly provided. See Figure 2 for vent hole location. This
hole location can be conveniently moved closer to unit exhaust
outlet tube to avoid wall stud interference if necessary. The orange
silicone exhaust elbow would need to be cut to length. Do not
locateventdirectlybehindtheexhaustoutlet. Donotusetheorange
silicone elbow for extended vent runs where the possibility of
flue condensate exists unless the run is horizontal and the elbow is
sloped downward away from the heater. See Figure 12 for extended
vertical venting.
Figure 6
WALL
KEEP CAP ON
MOUNTING PLATE
UN-USED AIR
INTAKE OPENING
The vent provided will accommodate walls up to 10" thick and
can be cut shorter for thinner walls if desired by using a hacksaw
or cut-off saw. Be sure to leave the minimum 3/4" of tube length
extending beyond the outside wall plate. Both the inner and outer
tube will be cut to the same length as the inner exhaust tube has an
extension piece which is added during final outside assembly.
INTAKE AIR
EXHAUST
EXHAUST ELBOW MAY
BE CUT TO LENGTH
TO FIT VENT BOX.
SECURE IN PLACE
USING HOSE CLAMPS
PROVIDED.
INTAKE FLEX HOSE
WITH CLAMPS
Figure 7
Page 10
19562-1-0606
FURNACE INSTALLATION (continued)
Be sure to deburr the ends with a file after cutting. Installation is
the vent system. In doing this, it is important to securely seal the
vent system and slope all horizontal runs downward 1/4" (6mm)
per foot (305mm) toward the vent terminal outside to drain out
any condensate. It is also necessary to adequately support both the
exhaust and intake and to center the exhaust pipe in the wall.
easy after cutting the wall opening secure the vent terminal box
in place using the (4) 10 x 1" hex-head screws provided. Locate
the box so that the middle exhaust tube is directed toward the
furnace exhaust outlet opening. See Figure 8. Attach the black 2"
flexible inlet air hose to the bottom 2" connector on the vent box
using a hose clamp. Secure the other end to the lower inlet air
box connector using the hose clamp. Do not kink hose. Attach the
long straight end of the 2" orange silicone exhaust elbow to the
middle vent terminal tube and rotate the elbow toward the furnace
exhaust outlet. Secure the hose to the vent box using a hose clamp.
Carefully push the furnace back closer to the wall and secure the
exhaust elbow to the 2" exhaust tube exiting the unit. Secure the
elbow in place using the last remaining hose clamp. The furnace
can now be secured to the wall.
Besuretoconsultlocalcodespriortoinstallationtoverifyallowable
procedures.
Installation of Shroud
To complete inside installation, secure furnace to the wall bracket
by attaching the two wall mounting brackets to the wall bracket
by using (2) 10 x 1/2" (13mm) hex-head screws provided (See
Figures 4 and 6). To attach the right shroud and left shroud to the
casing back, the 3/4" wide flange on the shroud must be positioned
toward the casing side. When positioned correctly, the (6) louvers
on the shroud will be facing up and the knock-out on the shroud
will be facing down. Attach the right shroud and left shroud to the
casingbackwith(3)10x1/2"hex-headscrewssuppliedinhardware
package, for each shroud. Attach top shroud to right shroud and
left shroud with (4) Phillips-head screws, supplied in hardware
package. Insert air filter into top shroud.
The furnace can be vented with up to a maximum length of 15'
(4.6m) including termination vent and using 2 - 90° elbows. Also,
the furnace can be vented with up to a maximum length of 10'
(3m) including termination vent and using 3 - 90° elbows. For
longer vent lengths order the vent kit, Part Number DVE-1 and
DVE-2. See Figures 11 and 12 illustrating extended vent run and
venting options.
Attention:Iftherightshroudandleftshroudareinstalledincorrectly,
with the 3/4" wide flanges facing inward, the top shroud will not
be able to be installed onto the side shrouds. The top shroud will
appear to be 2 inches, too narrow.
Note: If the extended vent kit is used and the exhaust vent pipe
is run through a cold space, such as an attic or a garage, the pipe
should be insulated using 1/2" (13mm) thick fiberglass insulation
or equivalent to keep the flue products warm enough to avoid
condensation. Also, slope 1/4" (6mm) per foot (305mm) the vent
terminal horizontal run downward toward the outside of the house
to assure any condensate flow out of vent system. Horizontal
vent pipe runs of 5 feet (1.5m) or more in length may accumulate
condensation in the exhaust pipe and must, therefore, be sloped
downward to drain any condensate out of the end vent terminal.
Use straps or other suitable supports spaced every 5 feet (1.5m) to
adequately hold pipe. Be sure to avoid any low spots or sags in
pipe run. Be sure all connections are tight using the hose clamps
as shown in Figure 9, "Vent Coupling Connections."
Vent Terminal (Figure 10)
Place the 6 3/8" x 6 3/8" (162mm x 162mm) black foam, wall plate
gasket within the mounting plate. The 4 3/4" (121mm) diameter
hole in the black foam gasket will allow for installation of the
concentricventtubeassembly.Slidetheoutsidemountingplateinto
place on the concentric vent tube assembly. The outside mounting
plate should seal against the face of the building and be secured
in place using (4) 10 x 1" hex-head screws. Be sure to caulk and
seal around the pipe on the exterior using high temperature exterior
grade, silicone caulk rated at 204°C/400°F. Wipe some silicone
sealant on the 2" (51mm) exhaust pipe extension. The end cap can
be pushed into place on the exhaust outlet tube.
For wall depths thicker than 10" (254mm) order the extended vent
terminal kit which will cover walls to 32" (813mm) thickness.
The vent pipes must be cut to length to assemble for desired wall
thickness.
Attention: The opening on the bottom of the end cap must be
positioned toward the ground. The opening on the bottom cannot
be pivoted to the right or left, it must be centered toward the
ground.
Forextendedventing,itisalsoacceptabletouse2"(51mm)diameter
PVC or ABS pipe for the combustion air intake supply piping
only to the unit. If this is used, the pipe and fittings must conform
to ANSI and ASTM Standards D1785 for SCH. 40 PVC, D2665
for PVC-DWV, D2241 for SDR-21 and SDR-26 PVC, D2661 for
ABS-DWV and F628 for SCH. 40 ABS. Pipe cement and primer
must be used and conform to ASTM Standard D2564 for PVC or
D2235 for ABS. This PVC or ABS pipe must not be used for
the exhaust vent pipe run.
NO. 10 X 1 1/2"
SCREWS (4)
INLET AIR
CAULK AROUND PIPE
EXHAUST FITTING-SLIDE ONTO
2" EXHAUST TUBE AND USE RTV
SEALANT TO SECURE IN PLACE
WITH OUTLET POINTED DOWN
AS SHOWN
Note: Type SDR pipe is not approved for use in Canada.
EXHAUST
AIR
12"(305mm)MIN.
ABOVE GRADE
For new construction installation, the intake and exhaust vent
can be run inside a wall, a vertical or horizontal distance prior to
exiting the wall. This can be done but not the preferred method of
installation due to the inability to perform periodic inspection of
Figure 10
19562-1-0606
Page 11
VENT TERMINAL
EXHAUST
INTAKE
SLOPE THE VENT TERMINAL
HORIZONTAL RUN DOWNWARD
THE OUTSIDE TO DRAIN OUT
ANY CONDENSATE
SLOPE DOWNWARD 1/4" (6mm)
PER FOOT (m) TO DRAIN ANY
CONDENSATE OUTSIDE
SUPPORT STAP EVERY
5 FT. (1.5m) MIN.
COUPLING WITH
HOSE CLAMPS
INTAKE AIR
EXHAUST AIR
ELBOW WITH CLAMPS
INTAKE AIR
EXHAUST AIR
INTERIOR WALL
SHROUD SIDE
Figure 12
FILTER
Reassembly and Resealing Vent-Air Intake System
When vent-air intake system is removed for servicing the furnace,
the following steps will assure proper reassembly and resealing
of the vent-air intake assembly. Be sure all hose connections and
elbow assemblies are re-secured in place using the hose clamps
removed. Reattachallscrewssecuringmountingflangesandinspect
all connections for a tight fit. Use high temperature silicone caulk
rated at 204°C/400°F to reseal the inlet air vent pipe and exhaust
TEMPERATURE CONTROL DOOR
Figure 11
Condensate Removal (Figures 11 and 12)
The condensate drain kit is used in conjunction with DVE and
DVE-2, intake/exhaust extension kits. The condensate drain kit is
required whenever there is a vertical vent run, in a heated room [10
ft. (3m) or more for DV-40E or 6 ft. (1.8m) or more for DV-20E],
in the intake/exhaust venting.
air vent pipe to the mounting plate.
Whenever a vertical vent run, in a heated room [10 ft. (3m) or more
for DV-40E or 6 ft. (1.8m) or more for DV-20E] and a horizontal
vent run are combined, you must purchase the optional condensate
drain kit, part number DV-1108. If the vertical vent run lengths are
less than those required for the condensate drain kit, you can slope
the horizontal vent run portion, downward 1/4" (6mm) per foot
(.3m) to the outside. However, if local codes prohibit condensate
from draining outside and the appliance produces condensate, the
horizontal portion of the vent run must slope downward, to the
appliance,1/4"(6mm)perfoot(.3m). Thiswillallowanycondensate
to flow into the condensate drain kit. Do not use the orange silicone
elbow supplied with unit to catch condensate. You can route the
condensate from the condensate drain kit to an existing drain or
into the condensate drain pan located within the appliance.
Whenever a horizontal vent run is used, where local codes allow,
you can slope the exhaust pipe downward, to the outside, 1/4"
(6mm) per foot (305mm). The downward slope on the exhaust
pipe will allow any condensate to flow out of the exhaust pipe. If
local codes prohibit condensate from draining to the outside and
the appliance produces condensate you must purchase condensate
drain kit, part number DV-1108.
Page 12
19562-1-0606
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result caus-
ing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner.
Do not try to light the burner by hand.
• If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in
or turn by hand, don't try to repair it; call a qualified
servicetechnician. Forceorattemptedrepairmayresult
in a fire or explosion.
B. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
D. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
5. Remove control access panel (front panel).
2. Set the thermostat to lowest setting.
6. Turn gas control knob clockwise
"OFF."
to
3. Turn off all electric power to the appliance.
7. Wait ten (10) minutes to clear out any gas.
Then smell for gas, including near the floor. If you smell
gas, STOP! Follow "B" in the safety information above.
If you don't smell gas, go to the next step.
4. This appliance is equipped with an ignition
device which automatically lights the burner. Do not try
to light the burner by hand.
8. Turn gas control knob counterclockwise
to "ON".
VINYL CAP
GAS CONTROL LEVER SHOWN
IN "OFF" POSITION
CONVERTIBLE
REGULATOR
9. Replace control access panel (front panel).
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
OFF
12. If the appliance will not operate, follow the instructions
"TO TURN OFF GAS TO APPLIANCE" and call your
service technician or gas supplier.
TOP VIEW
BACK END VIEW
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
4. Turn gas control knob clockwise
"OFF." Do not force.
to
2. Turn off all electric power to the appliance if
service is to be performed .
5. Replace control access panel (front panel).
3. Remove control access panel (front panel).
19562-1-0606
Page 13
WIRING
GV = GAS VALVE
LS = LIMIT SWITCH
FS = FLAME SENSOR
XFMR = TRANSFORMER
PS = PRESSURE SWITCH
IGN = HOT SURFACE IGNITOR
ROS = ROLLOUT LIMIT SWITCH
OPTIONAL WALL MOUNT THERMOSTAT
DISCONNECT INTEGRAL THERMOSTAT "R", "W", AND "C" LEADS AND ATTACH WALL THERMOSTAT AS SHOWN
CORDSET 115 VAC
XFMR
BLACK HOT
SMOOTH
INSULATION
BLACK NEUTRAL
RIBBED
INSULATION
W
R
ON/OFF
POWER SWITCH
GV
THERMOSTAT
ELECTRONIC
INTEGRAL
CIRCULATING AIR
BLOWER MOTOR
COMBUSTION AIR
INDUCER MOTOR
RED LED
STATUS
LIGHT
HOT SURFACE
IGNITOR
ORG
ORG
GRN
RED
9
8
7
6
5
4
3
2
1
FLAME SENSOR
IGN
RED
PRIMARY
115 VAC
TRANSFORMER
24 VAC
BLU
BLU
SECONDARY
COMMON
GND
3A FUSE
WHITE
BLACK
6
5
4
3
ON/OFF
2
1
THERMOSTAT
LIMIT
ROLLOUT
PRESSURE
SWITCH
GAS
VALVE
SWITCH LIMIT SWITCH
PUR
PUR
115 VAC
24 VOLT
FIELD INSTALLED
INDUCER
BLOWER
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED
WHT
BLK
WITH A WIRE OF AT LEAST 105
°
C TEMPERATURE RATING.
CIRCULATING AIR BLOWER
The appliance, when installed, must be electrically grounded in ac-
cordance with local codes or, in the absence of local codes, with the
NationalElectricalCode,ANSI/NFPA70orCanadianElectricalCode,
CSA C22.1, if an external electrical source is utilized. This appli-
ance is equipped with a three-prong [grounding] plug for your
protection against shock hazard and should be plugged directly
into a properly grounded three-prong receptacle. Do not cut or
remove the grounding prong from this plug. For an ungrounded
receptacle, an adapter, which has two prongs and a wire for ground-
ing, can be purchased, plugged into the ungrounded receptacle and
its wire connected to the receptacle mounting screw. With this wire
completing the ground, the appliance cord plug can be plugged into
the adapter and be electrically grounded.
to field locations different air currents may effect the control sensing
of the thermistor. This sensing bulb can be re-located if necessary to
provided for better room air sensing and control.
Replacement of Thermistor with 24 Volt Wall Thermostat
1. If furnace is installed, turn off gas supply and electric supply.
2. Remove casing front.
3. Remove black hose from front nipple on pressure switch.
4. Remove junction box cover (4 screws).
5. Please refer to wiring diagram for removal of the following
wires.
6. Internal Electronic Thermostat/Temperature Control
Board
Attention! No 24 volt wall thermostat wires are to be at-
tached to the internal electronic thermostat.
7. Control Board
A. Remove white wire form screw marked W.
B. Remove yellow wire from screw marked C.
C. Remove red wire from screw marked R.
8. Route (2) wires from any 24 volt wall thermostat through the
casing back of furnace to the screws marked W and R on the
control board.
CAUTION:Labelallwirespriortodisconnectionwhenservicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
Note: For testing flame sensor circuit use a micro-amp meter in
series with sensor. Minimum current should be 1 micro-amp dur-
ing operation. Be careful as flame sensor is in the 115VAC circuit.
If current is below 1 micro-amp, remove sensor, clean with light
sandpaper and retest.
9. Replace junction box cover (4 screws).
10. Replace black hose onto front nipple on pressure switch.
11. Replacement of thermistor with 24 volt wall thermostat is
completed.
Note:Thisheaterisequippedwitharemotebulbelectronicthermistor
control located down low at the back of the furnace. Sometimes due
Page 14
19562-1-0606
MAINTENANCE
Removing Gas Valve
Proper Main Burner Flame
1. Remove front grill assembly.
The proper main burner flame will be a blue primary (inner) flame
with a larger, lighter blue secondary (outer) blue flame.
2. Disconnect manifold union assembly at gas valve.
3. Remove (2) two 24 volt wires from gas valve. Label wires prior
to disconnection from gas valve.
4. Remove gas valve from gas valve bracket.
Removing Main Burner Orifice(s)
1. Remove front grill assembly.
2. Remove burner compartment access panel (2 screws).
3. Disconnect manifold union assembly.
4. Disconnect manifold union assembly brackets (5 screws).
Removing Ignitor and Flame Sensor
1. Remove front grill assembly.
2. Remove ignitor from burner compartment (2 screws).
3. Remove flame sensor from burner compartment (1 screw).
Cleaning Combustion (Exchanger) Assembly
A QUALIFIED SERVICE PERSON should remove the
combustion (exchanger) assembly. Apply air pressure to the
inside of the combustion (exchanger) assembly in order to clear
all passageways.
Figure 13
Cleaning Main Burner(s)
Remove main burner(s) and apply air pressure inside the throat and
ports of the main burner(s).
Removing Main Burner(s)
1. Remove front grill assembly.
2. Remove burner compartment access panel (2 screws).
3. Remove main burner(s) from burner compartment (2 screws
per main burner).
Oiling
The blower motor has an oil hole located on each end of the motor.
Use #20 motor oil only. It is best to oil the motor several times
during the heating season using 2 or 3 drops each time.
OPERATION AND TROUBLESHOOTING
Your new furnace should provide many years of trouble free
performance, however, a yearly inspection of the burners , flue
passageways and the outlet vent assembly should be done. Be
sure all passageways are open and clear of any obstruction, or soot
build up. Be sure to shut off all power to the unit while performing
this inspection.
The hot surface ignitor is energized and after a 17 second warm-
up, the gas valve circuit is energized, opening the gas valve
and igniting the burners. After burning for about 30 seconds,
the circulating air blower comes on, delivering warm air to
the room. If ignition does not occur, the ignition sequence is
repeated again up to 2 more times. (3 trials for ignition-total)
3. After the furnace operates and satisfies the thermostat, the gas
valve closes and the circulating air blower continues to run for
about 2 minutes and then shuts off. The inducer blower runs
for 5 seconds and shuts off.
Periodically remove the circulating air filter and clean with water
to remove all dirt. Shake dry and reinstall in unit.
System Operation
1. This furnace has an electronic thermostat and control board
to monitor the room temperature and then control the furnace
operation to provide the best comfort and performance from a
heating appliance. To operate unit turn ON/OFF switch to ON
and then turn temperature control knob clockwise slowly till
furnace turns on. For typical room comfort, the control knob
should be pointed toward medium.
2. The furnace control board follows sequence of operation which
allows for self diagnosis in the event there is a problem. The
control then blinks a status light, a set number of blinks based
on what problem has been encountered. When the furnace is
on and there is a no fault condition, the green LED is on.
On a typical call for heat by the integral thermostat 24 VAC is
applied to the W terminal on the board.
If for any reason ignition and operation does not occur, the
control board will blink the green fault status LED, a sequence
code, indicating what to look for as a troubleshooting guide.
If the green LED is ON but not blinking check the electronic
temperaturecontroltoverifyitsoperation.Thiscanbeeasilydone
bydisconnectingthe3electronictemperaturecontrolleadsfrom
the main furnace board and using a pig tail jumper to connect
R & W together on the board. If the furnace comes on and runs
normally the temperature control board is malfunctioning. If
the heater still does not come on, then the main furnace board
is malfunctioning. Look for any fault codes below and verify
the 3 amp fuse is not blown.
The inducer blower circuit is energized and the inducer blower
comes on for 15 seconds pre-purging out any gas and closing
the pressure switch.
19562-1-0606
Page 15
FURNACE CONTROL BOARD
DIAGNOSTICS
FAULT SEQUENCE CODE — TROUBLE SHOOTING GUIDE
# of Blinks Fault Condition
Fault Correction
Steady On
1 Flash
Control OK
Temperature limit switch is open
-Check Circulating Air Blower Inlet or Grill Outlet for Blockage, Inducer
Blower/Circulating Air Blower Run to Cool Heat Exchanger and Limit
-Check for Flame Roll Out Condition Causing Roll Out Limit Switch on
Burner Box to Open
-Clean Circulating Air Filter
2 Flashes
Pressure switch is open with inducer on
-Check Heat Exchanger and Flue System, Outlet and Inlet for Restriction
-Check Inducer Blower/Wheel for Operation/Airflow
-Check Pressure Switch
3 Flashes
4 Flashes
Pressure switch is closed with inducer off -Check Pressure Switch and Replace
Lockout due to failed ignition
-Check for Broken Ignitor
-Check for Bent Ignitor Bracket - Ignitor too far from Burner
-Check for Flame Sensor Malfunction/or False Ground
-Check Gas Valve
-Reset Thermostat
5 flashes
L1/Neutral reversed or voltage not present -Shut Off Power to Unit and Dis-Connect Cordset Plug from Wall Recep-
on L1
tacle.
Open Junction Box and Un-Reverse Polarity of Incoming Power Leads
Rapid Flash Flame sense or internal control fault
-Check Ignitor Operation
-Check Flame Sensor for Malfunction or False Grounding
-Check Gas Valve
-Reset Thermostat
Note: If the hot surface ignitor is to be replaced, be sure to disconnect all power to the unit. Be very careful in handling the new ignitor
as they are fragile and can be broken easily if hit or dropped.
Page 16
19562-1-0606
HOW TO ORDER REPAIR PARTS
Parts can be ordered only through your service person or dealer. For best results, the service person or dealer should order parts through
the distributor. Parts can be shipped directly to the service person/dealer.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your
equipment. Then determine the Part Number (not the Index Number) and the Description of each part from the following appropriate
illustration and list. Be sure to give all this information.
Furnace Model Number
Part Description
Part Number
Furnace Serial Number
Type of Gas (Propane or Natural)
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipments contingent upon strikes, fires and all causes beyond our control.
Empire Comfort Systems, Inc. Nine Eighteen Freeburg Ave. Belleville, IL 62222-0529
PARTS LIST
PLEASE NOTE: When ordering parts, it is very important that part number and description of part coincide.
INDEX
NO.
PART
NUMBER
INDEX
NO.
PART
NUMBER
DESCRIPTION
DESCRIPTION
1
2
3
4
5
6
7
8
9
DV-1378
DV-1376
R-2521
DV-1375
DV-1379
DV-1048
R-2586
19676
DV-1373
DV-1368
R-2584
R-2573
R-2598
R-1279
DV-1367
R-2546
R-2522
19561
DV-1370
R-1995
R-6989
R-8140
R-2577A
DV-1365
R-1468
R-2099
DV-1371
DV-1372
15790
SHROUD TOP
SHROUD SIDE RIGHT
AIR FILTER
39
40
R-2575
DV-1038
FLAME ROLLOUT SWITCH
BURNER COMPARTMENT ACCESS
PANEL
BURNER COMPARTMENT
GAS VALVE (NAT GAS)
GAS VALVE (LP GAS)
VALVE BRACKET ASSEMBLY
MANIFOLD ASSEMBLY (DV-20E-5 ONLY)
MANIFOLD ASSEMBLY (DV-40E-5 ONLY)
ORIFICE (NAT GAS) - 1 REQUIRED ON
DV-20E-5
ORIFICE (LPG GAS) - 1 REQUIRED ON
DV-20E-5
ORIFICE (NAT GAS) - 2 REQUIRED ON
DV-40E-5
ORIFICE (LPG GAS) - 2 REQUIRED ON
DV-40E-5
MANIFOLD GASKET
OBSERVATION HOLE COVER ASSEMBLY
OBSERVATION HOLE COVER GASKET
FRONT SHIELD ASSEMBLY
BOTTOM SHIELD
FRONT GRILL ASSEMBLY
CASING FRONT ASSEMBLY
HOSE CLAMP - 4 REQUIRED
INLET HOSE
FILTER RETAINER
41
42
42
43
44
44
45
DV-1039
R-3237
R-3238
DV-1366
DV-1016
DV-1013
P-88-44
WALL MOUNTING BRACKET
WALL BRACKET - 2 REQUIRED
CONTROL DOOR PIN - 2 REQUIRED
CONTROL DOOR ASSEMBLY
CASING TOP
BLOWER HOUSING - 2 REQUIRED
BLOWER WHEEL - 2 REQUIRED
BLOWER MOTOR
MOTOR BASE WASHER - 4 REQUIRED
LIMIT SWITCH
INNER TOP
CONTROL KNOB
ON/OFF SWITCH
JUNCTION BOX
JUNCTION BOX COVER
TRANSFORMER
PRESSURE SWITCH
CONTROL BOARD
TEMPERATURE CONTROL BOARD
CASING WELDED ASSEMBLY
STRAIN RELIEF BUSHING
CORD SET
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
29
30
31
32
33
33
34
37
38
45
45
45
P-88-55
P-88-44
P-88-55
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
NS
NS
NS
NS
M-148
DV-781
M-155
DV-1040
DV-1024
DV-1363
DV-1380
R-2539
R-3113
R-3111
DV-1192
R-3114
R-3115
INNER END
OUTLET ELBOW
VENT PAN ASSEMBLY
INLET CAP
WALL PLATE GASKET - INSIDE
WALL PLATE GASKET - OUTSIDE
WALL PLATE - OUTSIDE
TUBE SPACER
END CAP ASSEMBLY
SHROUD SIDE LEFT
CASING SIDE - 2 REQUIRED
COLLECTOR BOX (DV-20E-5 ONLY)
COLLECTOR BOX (DV-40E-5 ONLY)
INDUCER WHEEL
INDUCER BLOWER HOUSING
INDUCER MOTOR
EXCHANGER ASSEMBLY (DV-20E)
EXCHANGER ASSEMBLY (DV-40E)
IGNITOR KIT
15791
R-2519
DV-1169
R-2523
15783
15784
19565
R-2587
DV-1195
DV-1193
DV-1194
DV-1377
DV-1361
DV-1108
DV-1132
R-8142
BAFFLE - 1 REQUIRED ON DV-20E-5
CONDENSATE KIT
ELBOW KIT
R-2543
R-2541
FLAME SENSOR
BURNER (2 REQUIRED ON DV-40E-5)
WIRE ASSEMBLY - CONTROL BOARD
19562-1-0606
Page 17
PARTS VIEW
Page 18
19562-1-0606
SERVICE NOTES
19562-1-0606
Page 19
Empire Comfort Systems, Inc.
918 Freeburg Ave. Belleville, IL 62220
PH: 618-233-7420 or 800-851-3153
FAX: 618-233-7097 or 800-443-8648
Page 20
19562-1-0606
|