White Rodgers Heat Pump 1F59 13 User Manual

1F59-13  
Low Voltage Heat Pump Thermostat  
INSTALLATION & OPERATION  
INSTRUCTIONS  
WHITE-RODGERS  
Operator: Save these instructions for future use!  
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY  
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE  
PERSONAL INJURY AND/OR PROPERTY DAMAGE.  
DESCRIPTION  
These thermostats are designed to control a heat pump system  
where automatic changeover is not required.  
The 1F59-13 thermostat has no indicator lights.  
50  
60  
70  
80  
90  
70  
1F59-13  
PRECAUTIONS  
If in doubt about whether your wiring is millivolt, line, or low  
voltage, have it inspected by a qualified heating and air condi-  
tioning contractor or a licensed electrician.  
CAUTION  
!
To prevent electrical shock and/or equipment damage,  
disconnect electric power to system at main fuse or  
circuit breaker box until installation is complete.  
Do not exceed the specification ratings.  
All wiring must conform to local and national electrical codes  
and ordinances.  
WARNING  
!
This control is a precision instrument, and should be handled  
carefully.Roughhandlingordistortingcomponentscouldcause  
the control to malfunction.  
Do not use on circuits exceeding 30 volts. Higher  
voltage will damage control and could cause shock or  
fire hazard.  
DO NOT USE this thermostat on heat pump systems  
that have a spark ignition gas or fossil fuel second  
stage heat source.  
SPECIFICATIONS  
ELECTRICAL DATA  
THERMAL DATA  
Electrical Rating:  
Temperature Range: 40°F to 90°F (4°C to 32°C)  
18 to 30 VAC, 50/60 Hz  
0.01 to 1.5 amps (load per terminal)  
2.5 amps max. total load (all terminals combined)  
Rated Differential:  
Stage 1 heat – 1.3°F (max.)  
Stage 2 heat – 0.9°F (max.)  
Cooling – 1.3°F (max.)  
STAGING DATA  
DIMENSIONS  
Up to two heating stages  
3.5” H x 5.5” w x 1.25” D  
One cooling stage  
WHITE-RODGERS DIVISION  
EMERSON ELECTRIC CO.  
9797 REAVIS ROAD  
ST. LOUIS, MISSOURI 63123-5398  
PART NO. 37-5780A  
Printed in U.S.A.  
9713  
 
WIRE THERMOSTAT TO SYSTEM  
Insert stripped wires into terminal blocks,  
then tighten terminal screws.  
For best electrical connection, use solid 18 gauge wire. If you  
mustusestrandedwire, tinthewireswithsoldertoinsureagood  
electrical connection.  
1. Strip wires back 14”.  
W
R
G
O
Y
B
L
C
W7  
2. Using needle-nose pliers, insert wire into correct terminal  
block opening (see figs. 3 and 4).  
See  
System  
Function  
Table  
Anticipation  
Selection  
Switches  
3. Tighten terminal block connector screw.  
4. Repeat steps 2 and 3 for each wire.  
Pull wires through this opening  
Setpoint switch  
(without knob)  
Figure 3. Thermostat base with typical wiring  
CAUTION  
NOTE  
!
To prevent electrical shock and/or equipment damage,  
disconnect electrical power to system at main fuse or  
circuit breaker until installation is complete.  
Thistypicalwiringdiagramshowsonlytheterminalidentification  
and wiring hookup. Always refer to wiring instructions provided  
by equipment manufacturer for system hookup.  
All wiring should be installed in accordance with local and  
national codes and ordinances.  
Thermostat  
Control  
Circuit  
THERMOSTAT  
SYSTEM  
B
O
Y
G
W
C
L
R
Auxiliary  
Heat  
Relay  
Reversing  
Valve*  
Compressor  
Contactor  
Malfunction  
Switch  
Hot  
Fan  
Reversing  
Valve**  
120 VAC  
Neutral  
24 VAC  
Relay  
TRANSFORMER  
* Reversing valve is energized when the System Switch is in the HEAT position  
** Reversing valve is energized when the System Switch is in the COOL position  
Figure 4. Typical wiring diagram  
3. Carefully snap cover onto thermostat base. Refer to the  
ATTACH SETPOINT KNOB AND COVER  
OPERATION section for instructions on setting the thermo-  
stat for desired operation.  
1. Afterthermostatbaseismountedonwall, removecardboard  
insert from setpoint switch.  
2. Carefully press setpoint knob onto setpoint switch (see fig. 5).  
Setpoint  
Knob  
Setpoint  
Switch  
1
2
O
F
F
F
G
O
Y
1
2
O
F
F
5  
G
O
Y
5 5  
4 5 5 0  
4 0  
60  
62  
6465  
66  
5 5  
4 5 5 0  
4 0  
60  
9 0  
50  
62  
60  
8 8  
8 6  
8 4  
8 3  
8 2  
6465  
66  
70  
80  
68  
9 0  
90  
8 8  
8 6  
8 4  
8 3  
8 2  
69  
70  
71  
68  
7
69  
70  
71  
8 1  
8 0  
7 9  
72  
73  
74  
7 8  
77  
8 1  
8 0  
7 9  
72  
73  
74  
7 8  
77  
B
C
A
Figure 5. Attach setpoint knob and cover  
3
 
OPERATION  
SWITCH POSITIONS  
SYSTEM FUNCTION  
Rev  
Valve Valve  
(O) (B)  
Rev  
Aux  
Heat Compr.  
Relay Contact  
FAN  
SYSTEM  
Fan  
Emer Relay  
COMPONENT OPERATION  
Auto  
On  
Cool  
Off  
Heat  
No heat - no cool - no fan - no lights  
Heating Mode: stage 1 calling. Fan relay,  
compressor contactor, and reversing valve (B)  
energized by thermostat.  
Heating Mode: both stages calling. Fan relay,  
compressor contactor, reversing valve (B),  
and auxiliary heat relay are energized.  
Emergency Heat Mode: aux heat, Fan Relay*  
and reversing valve (B) are energized.  
Compressor locked out.  
Cooling Mode: Fan relay, compressor  
contactor and reversing valve (O) energized.  
Fan On: Energizes fan relay regardless  
of system switch position.  
Indicates switch position on thermostat subbase and system function in operation.  
* In EMERGENCY HEAT mode, fan may be disabled if required by cutting jumper W7 (see Fig 3)  
This thermostat is easy to operate. The above table shows how  
the system will operate when the FAN and SYSTEM switches  
are in different positions.  
FAN  
AUTO  
ON  
To set the switches, open the door on the left side of the  
thermostat (see fig 6). Move the FAN andSYSTEM switches up  
or down to select desired system operation. To set the tempera-  
ture, move the temperature selection knob (on the right side of  
the thermostat) until the desired temperature is shown in the  
70  
SYSTEM  
50 60 70 80 90  
COOL  
OFF  
HEAT  
EMER  
window.  
ANTICIPATION ADJUSTMENT  
Figure 6. Thermostat with door open  
The anticipation setting on this thermostat is adjustable. Any  
anticipation setting (including the factory setting) will work with  
any system for which this thermostat is intended for use.  
However, the user may be more comfortable with a particular  
setting. If the system is turning on and off too often (short cycles)  
or not often enough (long cycles) for the user’s comfort, follow  
these steps to adjust the anticipation.  
Antic.=14*  
Antic.=10* (Factory setting) Antic.=16*  
Antic.=30*  
1
2
1
2
1
2
1
2
OFF  
OFF  
OFF  
OFF  
Shorter  
Cycles  
Longer  
Cycles  
1. Turn off power to the thermostat.  
* These numbers represent different anticipation settings. See fig. 8 for  
further information.  
2. Remove the thermostat cover.  
3. Locate the anticipation adjustment switches (see fig. 3).  
Figure 7. Anticipation selection switch settings  
4. Usingapencilorsmallscrewdriver,movetheswitches  
to the desired setting (see figs. 7 and 8).  
First Stage Heat and Cool  
Second Stage and Emergency Heat  
Anticipation Approx.  
Anticipation  
Approx.  
5. Carefully snap the cover onto the thermostat base.  
6. Turn on power to the thermostat.  
Reference Temperature  
Reference Temperature  
Number  
10  
Differential*  
0.8°F  
Number  
10  
Differential*  
0.3°F  
14  
16  
1.1°F  
1.3°F  
14  
16  
0.4°F  
0.5°F  
30  
2.4°F  
30  
0.9°F  
* These numbers are approximate and represent thermostat operation with a typical  
system. Actual temperature differentials may vary.  
Figure 8. Approximate temperature differential and cycle times  
COMPRESSOR SHORT TERM CYCLE  
PROTECTION  
LOCKOUT BYPASS OPTION  
FOR QUALIFIED SERVICE TECHNICIANS’ USE ONLY.  
OPERATORS SHOULD NOT USE THIS FEATURE DUE  
TO POSSIBILITY OF EQUIPMENT DAMAGE, OR PER-  
SONAL INJURY.  
Thesethermostatshaveabuilt-inshortterm(5-minute)  
time delay. During this 5-minute period, the thermostat  
will lock out the compressor to allow heat pressure to  
stabilize. If you want to override this feature while  
testingthermostatoperation,movetheSYSTEMswitch  
to OFF. Wait about 6 to 8 seconds, then move the  
SYSTEM switch back to the previous position.  
DO NOT USE THE LOCKOUT BYPASS OPTION UN-  
LESS THE COMPRESSOR OIL HEATERS HAVE BEEN  
OPERATIONAL FOR AT LEAST 6 HOURS AND THE  
SYSTEM HAS NOT BEEN OPERATIONAL FOR AT  
LEAST 5 MINUTES.  
 

Weed Eater Tiller 168126 User Manual
Weslo Treadmill WLTL21280 User Manual
Westinghouse TV DVD Combo VK 40F580D User Manual
Whirlpool Air Conditioner CAW21D2A1 User Manual
Whirlpool Ventilation Hood GZ5730 User Manual
Winegard TV Receiver VS 0503 User Manual
Woodstock Saw W1673 User Manual
Zanussi Dishwasher ZT 6910 User Manual
Zanussi Washer FJ 1054 W User Manual
Zanussi Washer Z939T User Manual